LOGO

Selector Configurator ABB ACS800 drive selector and more...

Twitter
Home
Exit
ACS800
ACS800
ACS 800 Advanced control panel permitting intuitive operation Patented swinging choke for superior harmonic reduction (R1-R4) and AC line reactor (R5-R8) Sensorless vector control Integral EMC filter as standard Built-in Modbus RTU and numerous internally mountable fieldbus adapters FlashDrop Coated boards for harsh environments UL, cUL, C-Tick and Gost-R approved Built-in brake chopper (10Hp, 230V / 15Hp, 480V and 600 V) Many assistants including Start-up, Drive Optimizer, Real-time Clock, Diagnostics, Maintenance, Serial and PID Seismic Certification to ICC AC-156 Criteria
3AC 200V - 240V 50/60 Hz
Wall
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
1.1
5.1
No
No
R2
1.5
6.5
No
No
R2
1.5
8.5
No
No
R2
2.2
10.9
No
No
R2
3.0
13.9
No
No
R2
4.0
19.0
No
No
R3
5.5
25.0
No
No
R3
7.5
34.0
Yes
No
R5
7.5
34.0
No
No
R3
7.5
34.0
No
Yes
R5
11.0
44.0
No
No
R4
11.0
47.0
Yes
No
R5
11.0
47.0
No
Yes
R5
15.0
59.0
No
Yes
R5
15.0
59.0
Yes
No
R5
15.0
55.0
No
No
R4
18.5
72.0
No
No
R5
22.0
75.0
Yes
No
R5
22.0
75.0
No
Yes
R5
22.0
88.0
No
Yes
R5
22.0
88.0
Yes
No
R5
22.0
86.0
No
No
R5
30.0
103.0
No
No
R5
37.0
120.0
Yes
No
R6
37.0
120.0
No
Yes
R6
37.0
141.0
No
No
R6
45.0
150.0
No
Yes
R6
45.0
150.0
Yes
No
R6
45.0
169.0
Yes
No
R6
45.0
166.0
No
No
R6
45.0
169.0
No
Yes
R6
55.0
202.0
No
No
R6
3AC 380V - 415V 50/60 Hz
Wall
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
1.5
5.1
No
No
R2
2.2
6.5
No
No
R2
3.0
8.5
No
No
R2
4.0
10.9
No
No
R2
5.5
13.9
No
No
R2
7.5
19.0
No
No
R3
11.0
25.0
No
No
R3
15.0
34.0
No
No
R3
15.0
34.0
Yes
No
R5
15.0
34.0
No
Yes
R5
18.5
38.0
Yes
No
R5
18.5
38.0
No
Yes
R5
22.0
44.0
No
No
R4
22.0
47.0
No
Yes
R5
22.0
47.0
Yes
No
R5
30.0
55.0
No
No
R4
30.0
59.0
No
Yes
R5
30.0
59.0
Yes
No
R5
37.0
72.0
No
Yes
R5
37.0
72.0
Yes
No
R5
37.0
72.0
No
No
R5
45.0
86.0
Yes
No
R5
45.0
86.0
No
Yes
R5
45.0
86.0
No
No
R5
55.0
103.0
No
No
R5
55.0
120.0
No
Yes
R6
55.0
120.0
Yes
No
R6
75.0
150.0
No
Yes
R6
75.0
145.0
No
No
R5
75.0
150.0
Yes
No
R6
90.0
166.0
No
No
R6
90.0
165.0
No
Yes
R6
90.0
165.0
Yes
No
R6
110.0
225.0
No
No
R6
110.0
202.0
No
No
R6
132.0
260.0
No
No
R6
160.0
290.0
No
No
R6
3AC 380V - 500V 50/60 Hz
Wall
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
2.2
4.9
No
No
R2
3.0
6.2
No
No
R2
4.0
8.1
No
No
R2
5.5
10.5
No
No
R2
7.5
13.2
No
No
R2
11.0
19.0
No
No
R3
15.0
25.0
No
No
R3
18.5
31.0
No
Yes
R5
18.5
34.0
No
No
R3
18.5
31.0
Yes
No
R5
22.0
42.0
No
No
R4
22.0
36.0
Yes
No
R5
22.0
36.0
No
Yes
R5
30.0
48.0
No
No
R4
30.0
47.0
No
Yes
R5
30.0
47.0
Yes
No
R5
37.0
58.0
No
Yes
R5
37.0
58.0
Yes
No
R5
37.0
65.0
No
No
R5
45.0
70.0
Yes
No
R5
45.0
70.0
No
Yes
R5
45.0
79.0
No
No
R5
55.0
82.0
Yes
No
R5
55.0
82.0
No
Yes
R5
55.0
96.0
No
No
R5
75.0
120.0
Yes
No
R6
75.0
120.0
No
Yes
R6
90.0
139.0
No
Yes
R6
90.0
139.0
Yes
No
R6
90.0
145.0
No
No
R5
90.0
157.0
No
No
R6
110.0
156.0
Yes
No
R6
110.0
180.0
No
No
R6
110.0
156.0
No
Yes
R6
132.0
225.0
No
No
R6
160.0
260.0
No
No
R6
200.0
290.0
No
No
R6
3AC 525V - 690V 50/60 Hz
Wall
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
11.0
13.0
No
No
R4
15.0
17.0
No
No
R4
18.5
22.0
No
No
R4
22.0
25.0
No
No
R4
30.0
33.0
No
No
R4
30.0
36.0
No
No
R4
45.0
51.0
No
No
R5
55.0
57.0
No
Yes
R6
55.0
57.0
Yes
No
R6
55.0
57.0
No
No
R5
75.0
79.0
No
No
R6
75.0
79.0
No
Yes
R6
75.0
79.0
Yes
No
R6
90.0
93.0
Yes
No
R6
90.0
93.0
No
Yes
R6
90.0
93.0
No
No
R6
110.0
113.0
No
No
R6
132.0
134.0
No
No
R6
160.0
166.0
No
No
R6
160.0
190.0
No
No
R6
3AC 200V - 240V 50/60 Hz
Free-standing
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
55.0
214.0
No
No
R7
75.0
253.0
No
No
R7
90.0
295.0
No
No
R7
110.0
405.0
No
No
R8
132.0
447.0
No
No
R8
160.0
528.0
No
No
R8
160.0
613.0
No
No
R8
200.0
720.0
No
No
R8
200.0
693.0
No
No
R8
3AC 380V - 415V 50/60 Hz
Free-standing
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
110.0
206.0
No
No
R7
132.0
248.0
No
No
R7
160.0
289.0
No
No
R7
200.0
445.0
No
No
R8
250.0
521.0
No
No
R8
315.0
602.0
No
No
R8
355.0
693.0
No
No
R8
400.0
720.0
No
No
R8
3AC 380V - 500V 50/60 Hz
Free-standing
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
132.0
196.0
No
No
R7
160.0
245.0
No
No
R7
200.0
289.0
No
No
R7
250.0
440.0
No
No
R8
315.0
515.0
No
No
R8
355.0
550.0
No
No
R8
400.0
602.0
No
No
R8
450.0
684.0
No
No
R8
500.0
718.0
No
No
R8
3AC 525V - 690V 50/60 Hz
Free-standing
Order Nr.
Power.-kW
Curr. A
Low harmonics level
Regenerative
Size
132.0
134.0
No
No
R7
160.0
175.0
No
No
R7
160.0
166.0
No
No
R7
160.0
166.0
No
No
R7
315.0
315.0
No
No
R8
355.0
353.0
No
No
R8
400.0
396.0
No
No
R8
450.0
445.0
No
No
R8
500.0
488.0
No
No
R8
560.0
560.0
No
No
R8
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 5.1 A. Maximum output current 6.5 A. No-overload use . Power 1.1 kW. Light-overload . Current 4.7 A. Power 0.5 kW. Heavy-duty use . Current 3.4 A. Power 0.55 kW. Noise level 62 dBA. Heat dissipation 100 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 6.5 A. Maximum output current 8.2 A. No-overload use . Power 1.5 kW. Light-overload . Current 6 A. Power 1.1 kW. Heavy-duty use . Current 4.3 A. Power 0.75 kW. Noise level 62 dBA. Heat dissipation 100 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 8.5 A. Maximum output current 10.8 A. No-overload use . Power 1.5 kW. Light-overload . Current 7.7 A. Power 1.5 kW. Heavy-duty use . Current 5.7 A. Power 1.1 kW. Noise level 62 dBA. Heat dissipation 100 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 10.9 A. Maximum output current 13.8 A. No-overload use . Power 2.2 kW. Light-overload . Current 10.2 A. Power 2.2 kW. Heavy-duty use . Current 7.5 A. Power 1.5 kW. Noise level 62 dBA. Heat dissipation 120 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21. .
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 13.9 A. Maximum output current 17.6 A. No-overload use . Power 3 kW. Light-overload . Current 12.7 A. Power 3 kW. Heavy-duty use . Current 9.3 A. Power 2.2 kW. Noise level 62 dBA. Heat dissipation 140 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 19 A. Maximum output current 24 A. No-overload use . Power 4 kW. Light-overload . Current 18 A. Power 4 kW. Heavy-duty use . Current 14 A. Power 3 kW. Noise level 62 dBA. Heat dissipation 160 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 25 A. Maximum output current 32 A. No-overload use . Power 5.5 kW. Light-overload . Current 24 A. Power 5.5 kW. Heavy-duty use . Current 19 A. Power 4 kW. Noise level 62 dBA. Heat dissipation 200 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 34 A. Maximum output current 46 A. No-overload use . Power 7.5 kW. Light-overload . Current 31 A. Power 7.5 kW. Heavy-duty use . Current 23 A. Power 5.5 kW. Noise level 62 dBA. Heat dissipation 250 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 44 A. Maximum output current 62 A. No-overload use . Power 11 kW. Light-overload . Current 42 A. Power 11 kW. Heavy-duty use . Current 32 A. Power 7.5 kW. Noise level 62 dBA. Heat dissipation 340 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 55 A. Maximum output current 72 A. No-overload use . Power 15 kW. Light-overload . Current 50 A. Power 11 kW. Heavy-duty use . Current 37 A. Power 7.5 kW. Noise level 62 dBA. Heat dissipation 440 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 72 A. Maximum output current 86 A. No-overload use . Power 18.5 kW. Light-overload . Current 69 A. Power 18.5 kW. Heavy-duty use . Current 49 A. Power 11 kW. Noise level 65 dBA. Heat dissipation 530 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 86 A. Maximum output current 112 A. No-overload use . Power 22 kW. Light-overload . Current 80 A. Power 22 kW. Heavy-duty use . Current 60 A. Power 15 kW. Noise level 65 dBA. Heat dissipation 610 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 103 A. Maximum output current 138 A. No-overload use . Power 30 kW. Light-overload . Current 94 A. Power 22 kW. Heavy-duty use . Current 69 A. Power 18.5 kW. Noise level 65 dBA. Heat dissipation 810 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 141 A. Maximum output current 164 A. No-overload use . Power 37 kW. Light-overload . Current 132 A. Power 37 kW. Heavy-duty use . Current 97 A. Power 30 kW. Noise level 65 dBA. Heat dissipation 1190 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 166 A. Maximum output current 202 A. No-overload use . Power 45 kW. Light-overload . Current 155 A. Power 45 kW. Heavy-duty use . Current 115 A. Power 30 kW. Noise level 65 dBA. Heat dissipation 1190 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC200V-3AC240V . Rated current 202 A. Maximum output current 282 A. No-overload use . Power 55 kW. Light-overload . Current 184 A. Power 55 kW. Heavy-duty use . Current 141 A. Power 37 kW. Noise level 65 dBA. Heat dissipation 1440 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 5.1 A. Maximum output current 6.5 A. No-overload use . Power 1.5 kW. Light-overload . Current 4.7 A. Power 1.5 kW. Heavy-duty use . Current 3.4 A. Power 1.1 kW. Noise level 62 dBA. Heat dissipation 100 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 6.5 A. Maximum output current 8.2 A. No-overload use . Power 2.2 kW. Light-overload . Current 5.9 A. Power 2.2 kW. Heavy-duty use . Current 4.3 A. Power 1.5 kW. Noise level 62 dBA. Heat dissipation 120 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 8.5 A. Maximum output current 10.8 A. No-overload use . Power 3 kW. Light-overload . Current 7.7 A. Power 3 kW. Heavy-duty use . Current 5.7 A. Power 2.2 kW. Noise level 62 dBA. Heat dissipation 140 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 10.9 A. Maximum output current 13.8 A. No-overload use . Power 4 kW. Light-overload . Current 10.2 A. Power 4 kW. Heavy-duty use . Current 7.5 A. Power 3 kW. Noise level 62 dBA. Heat dissipation 160 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 13.9 A. Maximum output current 17.6 A. No-overload use . Power 5.5 kW. Light-overload . Current 12.7 A. Power 5.5 kW. Heavy-duty use . Current 9.3 A. Power 4 kW. Noise level 62 dBA. Heat dissipation 200 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 19 A. Maximum output current 24 A. No-overload use . Power 7.5 kW. Light-overload . Current 18 A. Power 7.5 kW. Heavy-duty use . Current 14 A. Power 5.5 kW. Noise level 62 dBA. Heat dissipation 250 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 25 A. Maximum output current 32 A. No-overload use . Power 11 kW. Light-overload . Current 24 A. Power 11 kW. Heavy-duty use . Current 19 A. Power 7.5 kW. Noise level 62 dBA. Heat dissipation 340 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 34 A. Maximum output current 46 A. No-overload use . Power 15 kW. Light-overload . Current 31 A. Power 15 kW. Heavy-duty use . Current 23 A. Power 11 kW. Noise level 62 dBA. Heat dissipation 440 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 44 A. Maximum output current 62 A. No-overload use . Power 22 kW. Light-overload . Current 41 A. Power 18.5 kW. Heavy-duty use . Current 32 A. Power 15 kW. Noise level 62 dBA. Heat dissipation 530 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 55 A. Maximum output current 72 A. No-overload use . Power 30 kW. Light-overload . Current 50 A. Power 22 kW. Heavy-duty use . Current 37 A. Power 18.5 kW. Noise level 62 dBA. Heat dissipation 610 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 72 A. Maximum output current 86 A. No-overload use . Power 37 kW. Light-overload . Current 69 A. Power 30 kW. Heavy-duty use . Current 49 A. Power 22 kW. Noise level 65 dBA. Heat dissipation 810 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 86 A. Maximum output current 112 A. No-overload use . Power 45 kW. Light-overload . Current 80 A. Power 37 kW. Heavy-duty use . Current 60 A. Power 30 kW. Noise level 65 dBA. Heat dissipation 990 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 103 A. Maximum output current 138 A. No-overload use . Power 55 kW. Light-overload . Current 94 A. Power 45 kW. Heavy-duty use . Current 69 A. Power 37 kW. Noise level 65 dBA. Heat dissipation 1190 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 145 A. Maximum output current 170 A. No-overload use . Power 75 kW. Light-overload . Current 141 A. Power 75 kW. Heavy-duty use . Current 100 A. Power 45 kW. Noise level 65 dBA. Heat dissipation 1440 W. Air flow 405 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 166 A. Maximum output current 202 A. No-overload use . Power 90 kW. Light-overload . Current 155 A. Power 75 kW. Heavy-duty use . Current 115 A. Power 55 kW. Noise level 65 dBA. Heat dissipation 1940 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 202 A. Maximum output current 282 A. No-overload use . Power 110 kW. Light-overload . Current 184 A. Power 90 kW. Heavy-duty use . Current 141 A. Power 75 kW. Noise level 65 dBA. Heat dissipation 2310 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 225 A. Maximum output current 326 A. No-overload use . Power 110 kW. Light-overload . Current 220 A. Power 110 kW. Heavy-duty use . Current 163 A. Power 90 kW. Noise level 65 dBA. Heat dissipation 2810 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 260 A. Maximum output current 326 A. No-overload use . Power 132 kW. Light-overload . Current 254 A. Power 132 kW. Heavy-duty use . Current 215 A. Power 110 kW. Noise level 65 dBA. Heat dissipation 3260 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC415V . Rated current 290 A. Maximum output current 351 A. No-overload use . Power 160 kW. Light-overload . Current 285 A. Power 160 kW. Heavy-duty use . Current 234 A. Power 132 kW. Noise level 65 dBA. Heat dissipation 4200 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 4.9 A. Maximum output current 6.5 A. No-overload use . Power 2.2 kW. Light-overload . Current 4.5 A. Power 2.2 kW. Heavy-duty use . Current 3.4 A. Power 1.5 kW. Noise level 62 dBA. Heat dissipation 120 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 6.2 A. Maximum output current 8.2 A. No-overload use . Power 3 kW. Light-overload . Current 5.6 A. Power 3 kW. Heavy-duty use . Current 4.2 A. Power 2.2 kW. Noise level 62 dBA. Heat dissipation 140 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 8.1 A. Maximum output current 10.8 A. No-overload use . Power 4 kW. Light-overload . Current 7.7 A. Power 4 kW. Heavy-duty use . Current 5.6 A. Power 3 kW. Noise level 62 dBA. Heat dissipation 160 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 10.5 A. Maximum output current 13.8 A. No-overload use . Power 5.5 kW. Light-overload . Current 10 A. Power 5.5 kW. Heavy-duty use . Current 7.5 A. Power 4 kW. Noise level 62 dBA. Heat dissipation 200 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 13.2 A. Maximum output current 17.6 A. No-overload use . Power 7.5 kW. Light-overload . Current 12 A. Power 7.5 kW. Heavy-duty use . Current 9.2 A. Power 5.5 kW. Noise level 62 dBA. Heat dissipation 250 W. Air flow 35 m3/h. Frame size R2. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 19 A. Maximum output current 24 A. No-overload use . Power 11 kW. Light-overload . Current 18 A. Power 11 kW. Heavy-duty use . Current 13 A. Power 7.5 kW. Noise level 62 dBA. Heat dissipation 340 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 25 A. Maximum output current 32 A. No-overload use . Power 15 kW. Light-overload . Current 23 A. Power 15 kW. Heavy-duty use . Current 18 A. Power 11 kW. Noise level 62 dBA. Heat dissipation 440 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 34 A. Maximum output current 46 A. No-overload use . Power 18.5 kW. Light-overload . Current 31 A. Power 18.5 kW. Heavy-duty use . Current 23 A. Power 15 kW. Noise level 62 dBA. Heat dissipation 530 W. Air flow 69 m3/h. Frame size R3. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 42 A. Maximum output current 62 A. No-overload use . Power 22 kW. Light-overload . Current 39 A. Power 22 kW. Heavy-duty use . Current 32 A. Power 18.5 kW. Noise level 62 dBA. Heat dissipation 610 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 48 A. Maximum output current 72 A. No-overload use . Power 30 kW. Light-overload . Current 44 A. Power 30 kW. Heavy-duty use . Current 36 A. Power 22 kW. Noise level 62 dBA. Heat dissipation 810 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 65 A. Maximum output current 86 A. No-overload use . Power 37 kW. Light-overload . Current 61 A. Power 37 kW. Heavy-duty use . Current 50 A. Power 30 kW. Noise level 65 dBA. Heat dissipation 990 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 79 A. Maximum output current 112 A. No-overload use . Power 45 kW. Light-overload . Current 75 A. Power 45 kW. Heavy-duty use . Current 60 A. Power 37 kW. Noise level 65 dBA. Heat dissipation 1190 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 96 A. Maximum output current 138 A. No-overload use . Power 55 kW. Light-overload . Current 88 A. Power 55 kW. Heavy-duty use . Current 69 A. Power 45 kW. Noise level 65 dBA. Heat dissipation 1440 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 145 A. Maximum output current 170 A. No-overload use . Power 90 kW. Light-overload . Current 141 A. Power 90 kW. Heavy-duty use . Current 100 A. Power 55 kW. Noise level 65 dBA. Heat dissipation 2150 W. Air flow 405 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 157 A. Maximum output current 202 A. No-overload use . Power 90 kW. Light-overload . Current 145 A. Power 90 kW. Heavy-duty use . Current 113 A. Power 75 kW. Noise level 65 dBA. Heat dissipation 2310 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 180 A. Maximum output current 282 A. No-overload use . Power 110 kW. Light-overload . Current 163 A. Power 110 kW. Heavy-duty use . Current 141 A. Power 90 kW. Noise level 65 dBA. Heat dissipation 2810 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 225 A. Maximum output current 326 A. No-overload use . Power 132 kW. Light-overload . Current 220 A. Power 132 kW. Heavy-duty use . Current 163 A. Power 110 kW. Noise level 65 dBA. Heat dissipation 3260 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 260 A. Maximum output current 326 A. No-overload use . Power 160 kW. Light-overload . Current 254 A. Power 160 kW. Heavy-duty use . Current 215 A. Power 132 kW. Noise level 65 dBA. Heat dissipation 3800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC380V-3AC500V . Rated current 290 A. Maximum output current 351 A. No-overload use . Power 200 kW. Light-overload . Current 285 A. Power 200 kW. Heavy-duty use . Current 234 A. Power 160 kW. Noise level 65 dBA. Heat dissipation 4500 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 13 A. Maximum output current 14 A. No-overload use . Power 11 kW. Light-overload . Current 11.5 A. Power 7.5 kW. Heavy-duty use . Current 8.5 A. Power 5.5 kW. Noise level 62 dBA. Heat dissipation 300 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 17 A. Maximum output current 19 A. No-overload use . Power 15 kW. Light-overload . Current 15 A. Power 11 kW. Heavy-duty use . Current 11 A. Power 7.5 kW. Noise level 62 dBA. Heat dissipation 340 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 22 A. Maximum output current 28 A. No-overload use . Power 18.5 kW. Light-overload . Current 20 A. Power 15 kW. Heavy-duty use . Current 15 A. Power 11 kW. Noise level 62 dBA. Heat dissipation 440 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 25 A. Maximum output current 38 A. No-overload use . Power 22 kW. Light-overload . Current 23 A. Power 18.5 kW. Heavy-duty use . Current 19 A. Power 15 kW. Noise level 62 dBA. Heat dissipation 530 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 33 A. Maximum output current 44 A. No-overload use . Power 30 kW. Light-overload . Current 30 A. Power 22 kW. Heavy-duty use . Current 22 A. Power 18.5 kW. Noise level 62 dBA. Heat dissipation 610 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 36 A. Maximum output current 54 A. No-overload use . Power 30 kW. Light-overload . Current 34 A. Power 30 kW. Heavy-duty use . Current 27 A. Power 22 kW. Noise level 62 dBA. Heat dissipation 690 W. Air flow 103 m3/h. Frame size R4. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 51 A. Maximum output current 68 A. No-overload use . Power 45 kW. Light-overload . Current 46 A. Power 37 kW. Heavy-duty use . Current 34 A. Power 30 kW. Noise level 65 dBA. Heat dissipation 840 W. Air flow 250 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 57 A. Maximum output current 84 A. No-overload use . Power 55 kW. Light-overload . Current 52 A. Power 45 kW. Heavy-duty use . Current 42 A. Power 37 kW. Noise level 65 dBA. Heat dissipation 1010 W. Air flow 405 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 79 A. Maximum output current 104 A. No-overload use . Power 75 kW. Light-overload . Current 73 A. Power 55 kW. Heavy-duty use . Current 54 A. Power 45 kW. Noise level 65 dBA. Heat dissipation 1220 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 93 A. Maximum output current 124 A. No-overload use . Power 90 kW. Light-overload . Current 86 A. Power 75 kW. Heavy-duty use . Current 62 A. Power 55 kW. Noise level 65 dBA. Heat dissipation 1650 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 113 A. Maximum output current 172 A. No-overload use . Power 110 kW. Light-overload . Current 108 A. Power 90 kW. Heavy-duty use . Current 86 A. Power 75 kW. Noise level 65 dBA. Heat dissipation 1960 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 134 A. Maximum output current 190 A. No-overload use . Power 132 kW. Light-overload . Current 125 A. Power 110 kW. Heavy-duty use . Current 95 A. Power 90 kW. Noise level 65 dBA. Heat dissipation 2660 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 166 A. Maximum output current 245 A. No-overload use . Power 160 kW. Light-overload . Current 155 A. Power 132 kW. Heavy-duty use . Current 131 A. Power 110 kW. Noise level 65 dBA. Heat dissipation 3470 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -01. Type Wall-mounted drives. Voltage 3AC525V-3AC690V . Rated current 190 A. Maximum output current 245 A. No-overload use . Power 160 kW. Light-overload . Current 180 A. Power 160 kW. Heavy-duty use . Current 147 A. Power 132 kW. Noise level 65 dBA. Heat dissipation 4180 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 34 A. Maximum output current 52 A. No-overload use . Power 7.5 kW. Light-overload . Current 32 A. Power 7.5 kW. Heavy-duty use . Current 26 A. Power 5.5 kW. Noise level 70 dBA. Heat dissipation 505 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 47 A. Maximum output current 68 A. No-overload use . Power 11 kW. Light-overload . Current 45 A. Power 11 kW. Heavy-duty use . Current 38 A. Power 7.5 kW. Noise level 70 dBA. Heat dissipation 694 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 59 A. Maximum output current 90 A. No-overload use . Power 15 kW. Light-overload . Current 56 A. Power 15 kW. Heavy-duty use . Current 45 A. Power 11 kW. Noise level 70 dBA. Heat dissipation 910 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 75 A. Maximum output current 118 A. No-overload use . Power 22 kW. Light-overload . Current 69 A. Power 18.5 kW. Heavy-duty use . Current 59 A. Power 15 kW. Noise level 70 dBA. Heat dissipation 1099 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 88 A. Maximum output current 137 A. No-overload use . Power 22 kW. Light-overload . Current 83 A. Power 22 kW. Heavy-duty use . Current 72 A. Power 18.5 kW. Noise level 70 dBA. Heat dissipation 1315 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 120 A. Maximum output current 168 A. No-overload use . Power 37 kW. Light-overload . Current 114 A. Power 30 kW. Heavy-duty use . Current 84 A. Power 22 kW. Noise level 73 dBA. Heat dissipation 1585 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 150 A. Maximum output current 234 A. No-overload use . Power 45 kW. Light-overload . Current 143 A. Power 45 kW. Heavy-duty use . Current 117 A. Power 30 kW. Noise level 73 dBA. Heat dissipation 2125 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC200V-3AC240V . Rated current 169 A. Maximum output current 264 A. No-overload use . Power 45 kW. Light-overload . Current 157 A. Power 45 kW. Heavy-duty use . Current 132 A. Power 37 kW. Noise level 73 dBA. Heat dissipation 2530 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 34 A. Maximum output current 52 A. No-overload use . Power 15 kW. Light-overload . Current 32 A. Power 15 kW. Heavy-duty use . Current 26 A. Power 11 kW. Noise level 70 dBA. Heat dissipation 550 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 38 A. Maximum output current 61 A. No-overload use . Power 18.5 kW. Light-overload . Current 36 A. Power 18.5 kW. Heavy-duty use . Current 34 A. Power 15 kW. Noise level 70 dBA. Heat dissipation 655 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 47 A. Maximum output current 68 A. No-overload use . Power 22 kW. Light-overload . Current 45 A. Power 22 kW. Heavy-duty use . Current 38 A. Power 18.5 kW. Noise level 70 dBA. Heat dissipation 760 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 59 A. Maximum output current 90 A. No-overload use . Power 30 kW. Light-overload . Current 56 A. Power 30 kW. Heavy-duty use . Current 45 A. Power 22 kW. Noise level 70 dBA. Heat dissipation 1000 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 72 A. Maximum output current 118 A. No-overload use . Power 37 kW. Light-overload . Current 69 A. Power 37 kW. Heavy-duty use . Current 59 A. Power 30 kW. Noise level 70 dBA. Heat dissipation 1210 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 86 A. Maximum output current 137 A. No-overload use . Power 45 kW. Light-overload . Current 83 A. Power 45 kW. Heavy-duty use . Current 65 A. Power 30 kW. Noise level 70 dBA. Heat dissipation 1450 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 120 A. Maximum output current 168 A. No-overload use . Power 55 kW. Light-overload . Current 114 A. Power 55 kW. Heavy-duty use . Current 88 A. Power 45 kW. Noise level 73 dBA. Heat dissipation 1750 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 150 A. Maximum output current 234 A. No-overload use . Power 75 kW. Light-overload . Current 143 A. Power 75 kW. Heavy-duty use . Current 117 A. Power 55 kW. Noise level 73 dBA. Heat dissipation 2350 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC415V . Rated current 165 A. Maximum output current 264 A. No-overload use . Power 90 kW. Light-overload . Current 157 A. Power 75 kW. Heavy-duty use . Current 132 A. Power 75 kW. Noise level 73 dBA. Heat dissipation 2800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 31 A. Maximum output current 52 A. No-overload use . Power 18.5 kW. Light-overload . Current 29 A. Power 18.5 kW. Heavy-duty use . Current 25 A. Power 15 kW. Noise level 70 dBA. Heat dissipation 655 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 36 A. Maximum output current 61 A. No-overload use . Power 22 kW. Light-overload . Current 34 A. Power 22 kW. Heavy-duty use . Current 30 A. Power 18.5 kW. Noise level 70 dBA. Heat dissipation 760 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 47 A. Maximum output current 68 A. No-overload use . Power 30 kW. Light-overload . Current 45 A. Power 30 kW. Heavy-duty use . Current 37 A. Power 22 kW. Noise level 70 dBA. Heat dissipation 1000 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 58 A. Maximum output current 90 A. No-overload use . Power 37 kW. Light-overload . Current 55 A. Power 37 kW. Heavy-duty use . Current 47 A. Power 30 kW. Noise level 70 dBA. Heat dissipation 1210 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 70 A. Maximum output current 118 A. No-overload use . Power 45 kW. Light-overload . Current 67 A. Power 45 kW. Heavy-duty use . Current 57 A. Power 37 kW. Noise level 70 dBA. Heat dissipation 1450 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 82 A. Maximum output current 130 A. No-overload use . Power 55 kW. Light-overload . Current 78 A. Power 45 kW. Heavy-duty use . Current 62 A. Power 37 kW. Noise level 70 dBA. Heat dissipation 1750 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 120 A. Maximum output current 168 A. No-overload use . Power 75 kW. Light-overload . Current 114 A. Power 75 kW. Heavy-duty use . Current 88 A. Power 55 kW. Noise level 73 dBA. Heat dissipation 2350 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 139 A. Maximum output current 234 A. No-overload use . Power 90 kW. Light-overload . Current 132 A. Power 90 kW. Heavy-duty use . Current 114 A. Power 75 kW. Noise level 73 dBA. Heat dissipation 2800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC380V-3AC500V . Rated current 156 A. Maximum output current 264 A. No-overload use . Power 110 kW. Light-overload . Current 148 A. Power 90 kW. Heavy-duty use . Current 125 A. Power 75 kW. Noise level 73 dBA. Heat dissipation 3400 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC525V-3AC690V . Rated current 57 A. Maximum output current 86 A. No-overload use . Power 55 kW. Light-overload . Current 54 A. Power 45 kW. Heavy-duty use . Current 43 A. Power 37 kW. Noise level 76 dBA. Heat dissipation 1750 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC525V-3AC690V . Rated current 79 A. Maximum output current 120 A. No-overload use . Power 75 kW. Light-overload . Current 75 A. Power 55 kW. Heavy-duty use . Current 60 A. Power 55 kW. Noise level 76 dBA. Heat dissipation 2350 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -11. Type Wall-mounted regenerative drives. Voltage 3AC525V-3AC690V . Rated current 93 A. Maximum output current 142 A. No-overload use . Power 90 kW. Light-overload . Current 88 A. Power 75 kW. Heavy-duty use . Current 71 A. Power 55 kW. Noise level 76 dBA. Heat dissipation 2800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 34 A. Maximum output current 52 A. No-overload use . Power 7.5 kW. Light-overload . Current 32 A. Power 7.5 kW. Heavy-duty use . Current 26 A. Power 5.5 kW. Noise level 70 dBA. Heat dissipation 505 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 47 A. Maximum output current 68 A. No-overload use . Power 11 kW. Light-overload . Current 45 A. Power 11 kW. Heavy-duty use . Current 38 A. Power 7.5 kW. Noise level 70 dBA. Heat dissipation 694 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 59 A. Maximum output current 90 A. No-overload use . Power 15 kW. Light-overload . Current 56 A. Power 15 kW. Heavy-duty use . Current 45 A. Power 11 kW. Noise level 70 dBA. Heat dissipation 910 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 75 A. Maximum output current 118 A. No-overload use . Power 22 kW. Light-overload . Current 69 A. Power 18.5 kW. Heavy-duty use . Current 59 A. Power 15 kW. Noise level 70 dBA. Heat dissipation 1099 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 88 A. Maximum output current 137 A. No-overload use . Power 22 kW. Light-overload . Current 83 A. Power 22 kW. Heavy-duty use . Current 72 A. Power 18.5 kW. Noise level 70 dBA. Heat dissipation 1315 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 120 A. Maximum output current 168 A. No-overload use . Power 37 kW. Light-overload . Current 114 A. Power 30 kW. Heavy-duty use . Current 84 A. Power 22 kW. Noise level 73 dBA. Heat dissipation 1585 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 150 A. Maximum output current 234 A. No-overload use . Power 45 kW. Light-overload . Current 143 A. Power 45 kW. Heavy-duty use . Current 117 A. Power 30 kW. Noise level 73 dBA. Heat dissipation 2125 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC200V-3AC240V . Rated current 169 A. Maximum output current 264 A. No-overload use . Power 45 kW. Light-overload . Current 157 A. Power 45 kW. Heavy-duty use . Current 132 A. Power 37 kW. Noise level 73 dBA. Heat dissipation 2530 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 34 A. Maximum output current 52 A. No-overload use . Power 15 kW. Light-overload . Current 32 A. Power 15 kW. Heavy-duty use . Current 26 A. Power 11 kW. Noise level 70 dBA. Heat dissipation 550 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 38 A. Maximum output current 61 A. No-overload use . Power 18.5 kW. Light-overload . Current 36 A. Power 18.5 kW. Heavy-duty use . Current 34 A. Power 15 kW. Noise level 70 dBA. Heat dissipation 655 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 47 A. Maximum output current 68 A. No-overload use . Power 22 kW. Light-overload . Current 45 A. Power 22 kW. Heavy-duty use . Current 38 A. Power 18.5 kW. Noise level 70 dBA. Heat dissipation 760 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 59 A. Maximum output current 90 A. No-overload use . Power 30 kW. Light-overload . Current 56 A. Power 30 kW. Heavy-duty use . Current 45 A. Power 22 kW. Noise level 70 dBA. Heat dissipation 1000 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 72 A. Maximum output current 118 A. No-overload use . Power 37 kW. Light-overload . Current 69 A. Power 37 kW. Heavy-duty use . Current 59 A. Power 30 kW. Noise level 70 dBA. Heat dissipation 1210 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 86 A. Maximum output current 137 A. No-overload use . Power 45 kW. Light-overload . Current 83 A. Power 45 kW. Heavy-duty use . Current 65 A. Power 30 kW. Noise level 70 dBA. Heat dissipation 1450 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 120 A. Maximum output current 168 A. No-overload use . Power 55 kW. Light-overload . Current 114 A. Power 55 kW. Heavy-duty use . Current 88 A. Power 45 kW. Noise level 73 dBA. Heat dissipation 1750 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 150 A. Maximum output current 234 A. No-overload use . Power 75 kW. Light-overload . Current 143 A. Power 75 kW. Heavy-duty use . Current 117 A. Power 55 kW. Noise level 73 dBA. Heat dissipation 2350 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC415V . Rated current 165 A. Maximum output current 264 A. No-overload use . Power 90 kW. Light-overload . Current 157 A. Power 75 kW. Heavy-duty use . Current 132 A. Power 75 kW. Noise level 73 dBA. Heat dissipation 2800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 31 A. Maximum output current 52 A. No-overload use . Power 18.5 kW. Light-overload . Current 29 A. Power 18.5 kW. Heavy-duty use . Current 25 A. Power 15 kW. Noise level 70 dBA. Heat dissipation 655 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 36 A. Maximum output current 61 A. No-overload use . Power 22 kW. Light-overload . Current 34 A. Power 22 kW. Heavy-duty use . Current 30 A. Power 18.5 kW. Noise level 70 dBA. Heat dissipation 760 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 47 A. Maximum output current 68 A. No-overload use . Power 30 kW. Light-overload . Current 45 A. Power 30 kW. Heavy-duty use . Current 37 A. Power 22 kW. Noise level 70 dBA. Heat dissipation 1000 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 58 A. Maximum output current 90 A. No-overload use . Power 37 kW. Light-overload . Current 55 A. Power 37 kW. Heavy-duty use . Current 47 A. Power 30 kW. Noise level 70 dBA. Heat dissipation 1210 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 70 A. Maximum output current 118 A. No-overload use . Power 45 kW. Light-overload . Current 67 A. Power 45 kW. Heavy-duty use . Current 57 A. Power 37 kW. Noise level 70 dBA. Heat dissipation 1450 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 82 A. Maximum output current 130 A. No-overload use . Power 55 kW. Light-overload . Current 78 A. Power 45 kW. Heavy-duty use . Current 62 A. Power 37 kW. Noise level 70 dBA. Heat dissipation 1750 W. Air flow 350 m3/h. Frame size R5. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 120 A. Maximum output current 168 A. No-overload use . Power 75 kW. Light-overload . Current 114 A. Power 75 kW. Heavy-duty use . Current 88 A. Power 55 kW. Noise level 73 dBA. Heat dissipation 2350 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 139 A. Maximum output current 234 A. No-overload use . Power 90 kW. Light-overload . Current 132 A. Power 90 kW. Heavy-duty use . Current 114 A. Power 75 kW. Noise level 73 dBA. Heat dissipation 2800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC380V-3AC500V . Rated current 156 A. Maximum output current 264 A. No-overload use . Power 110 kW. Light-overload . Current 148 A. Power 90 kW. Heavy-duty use . Current 125 A. Power 75 kW. Noise level 73 dBA. Heat dissipation 3400 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC525V-3AC690V . Rated current 57 A. Maximum output current 86 A. No-overload use . Power 55 kW. Light-overload . Current 54 A. Power 45 kW. Heavy-duty use . Current 43 A. Power 37 kW. Noise level 76 dBA. Heat dissipation 1750 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC525V-3AC690V . Rated current 79 A. Maximum output current 120 A. No-overload use . Power 75 kW. Light-overload . Current 75 A. Power 55 kW. Heavy-duty use . Current 60 A. Power 55 kW. Noise level 76 dBA. Heat dissipation 2350 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -31. Type Wall-mounted low harmonic drives. Voltage 3AC525V-3AC690V . Rated current 93 A. Maximum output current 142 A. No-overload use . Power 90 kW. Light-overload . Current 88 A. Power 75 kW. Heavy-duty use . Current 71 A. Power 55 kW. Noise level 76 dBA. Heat dissipation 2800 W. Air flow 405 m3/h. Frame size R6. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 214 A. Maximum output current 326 A. No-overload use . Power 55 kW. Light-overload . Current 211 A. Power 55 kW. Heavy-duty use . Current 170 A. Power 45 kW. Noise level 71 dBA. Heat dissipation 2900 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 253 A. Maximum output current 404 A. No-overload use . Power 75 kW. Light-overload . Current 248 A. Power 75 kW. Heavy-duty use . Current 202 A. Power 55 kW. Noise level 71 dBA. Heat dissipation 3450 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 295 A. Maximum output current 432 A. No-overload use . Power 90 kW. Light-overload . Current 290 A. Power 90 kW. Heavy-duty use . Current 240 A. Power 55 kW. Noise level 71 dBA. Heat dissipation 4050 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 405 A. Maximum output current 588 A. No-overload use . Power 110 kW. Light-overload . Current 396 A. Power 110 kW. Heavy-duty use . Current 316 A. Power 90 kW. Noise level 72 dBA. Heat dissipation 5300 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 447 A. Maximum output current 588 A. No-overload use . Power 132 kW. Light-overload . Current 440 A. Power 132 kW. Heavy-duty use . Current 340 A. Power 90 kW. Noise level 72 dBA. Heat dissipation 6100 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 528 A. Maximum output current 588 A. No-overload use . Power 160 kW. Light-overload . Current 516 A. Power 160 kW. Heavy-duty use . Current 370 A. Power 110 kW. Noise level 72 dBA. Heat dissipation 6700 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 613 A. Maximum output current 840 A. No-overload use . Power 160 kW. Light-overload . Current 598 A. Power 160 kW. Heavy-duty use . Current 480 A. Power 132 kW. Noise level 72 dBA. Heat dissipation 7600 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 693 A. Maximum output current 1017 A. No-overload use . Power 200 kW. Light-overload . Current 679 A. Power 200 kW. Heavy-duty use . Current 590 A. Power 160 kW. Noise level 72 dBA. Heat dissipation 7850 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC200V-3AC240V . Rated current 720 A. Maximum output current 1017 A. No-overload use . Power 200 kW. Light-overload . Current 704 A. Power 200 kW. Heavy-duty use . Current 635 A. Power 200 kW. Noise level 72 dBA. Heat dissipation 8300 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 206 A. Maximum output current 326 A. No-overload use . Power 110 kW. Light-overload . Current 202 A. Power 110 kW. Heavy-duty use . Current 163 A. Power 90 kW. Noise level 71 dBA. Heat dissipation 3000 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 248 A. Maximum output current 404 A. No-overload use . Power 132 kW. Light-overload . Current 243 A. Power 132 kW. Heavy-duty use . Current 202 A. Power 110 kW. Noise level 71 dBA. Heat dissipation 3650 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 289 A. Maximum output current 432 A. No-overload use . Power 160 kW. Light-overload . Current 284 A. Power 160 kW. Heavy-duty use . Current 240 A. Power 132 kW. Noise level 71 dBA. Heat dissipation 4300 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 445 A. Maximum output current 588 A. No-overload use . Power 200 kW. Light-overload . Current 440 A. Power 200 kW. Heavy-duty use . Current 340 A. Power 160 kW. Noise level 72 dBA. Heat dissipation 6600 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 521 A. Maximum output current 588 A. No-overload use . Power 250 kW. Light-overload . Current 516 A. Power 250 kW. Heavy-duty use . Current 370 A. Power 200 kW. Noise level 72 dBA. Heat dissipation 7150 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 602 A. Maximum output current 840 A. No-overload use . Power 315 kW. Light-overload . Current 590 A. Power 315 kW. Heavy-duty use . Current 477 A. Power 250 kW. Noise level 72 dBA. Heat dissipation 8100 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 693 A. Maximum output current 1017 A. No-overload use . Power 355 kW. Light-overload . Current 679 A. Power 355 kW. Heavy-duty use . Current 590 A. Power 315 kW. Noise level 72 dBA. Heat dissipation 8650 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC415V . Rated current 720 A. Maximum output current 1017 A. No-overload use . Power 400 kW. Light-overload . Current 704 A. Power 400 kW. Heavy-duty use . Current 635 A. Power 355 kW. Noise level 72 dBA. Heat dissipation 9100 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 196 A. Maximum output current 326 A. No-overload use . Power 132 kW. Light-overload . Current 192 A. Power 132 kW. Heavy-duty use . Current 162 A. Power 110 kW. Noise level 71 dBA. Heat dissipation 3000 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 245 A. Maximum output current 384 A. No-overload use . Power 160 kW. Light-overload . Current 240 A. Power 160 kW. Heavy-duty use . Current 192 A. Power 132 kW. Noise level 71 dBA. Heat dissipation 3800 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 289 A. Maximum output current 432 A. No-overload use . Power 200 kW. Light-overload . Current 284 A. Power 200 kW. Heavy-duty use . Current 224 A. Power 160 kW. Noise level 71 dBA. Heat dissipation 4500 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 440 A. Maximum output current 588 A. No-overload use . Power 250 kW. Light-overload . Current 435 A. Power 250 kW. Heavy-duty use . Current 340 A. Power 200 kW. Noise level 72 dBA. Heat dissipation 6850 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 515 A. Maximum output current 588 A. No-overload use . Power 315 kW. Light-overload . Current 510 A. Power 315 kW. Heavy-duty use . Current 370 A. Power 250 kW. Noise level 72 dBA. Heat dissipation 7800 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 550 A. Maximum output current 840 A. No-overload use . Power 355 kW. Light-overload . Current 545 A. Power 355 kW. Heavy-duty use . Current 490 A. Power 315 kW. Noise level 72 dBA. Heat dissipation 7600 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 602 A. Maximum output current 840 A. No-overload use . Power 400 kW. Light-overload . Current 590 A. Power 400 kW. Heavy-duty use . Current 515 A. Power 355 kW. Noise level 72 dBA. Heat dissipation 8100 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 684 A. Maximum output current 1017 A. No-overload use . Power 450 kW. Light-overload . Current 670 A. Power 450 kW. Heavy-duty use . Current 590 A. Power 400 kW. Noise level 72 dBA. Heat dissipation 9100 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC380V-3AC500V . Rated current 718 A. Maximum output current 1017 A. No-overload use . Power 500 kW. Light-overload . Current 704 A. Power 500 kW. Heavy-duty use . Current 632 A. Power 450 kW. Noise level 72 dBA. Heat dissipation 9700 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 134 A. Maximum output current 190 A. No-overload use . Power 132 kW. Light-overload . Current 125 A. Power 110 kW. Heavy-duty use . Current 95 A. Power 90 kW. Noise level 71 dBA. Heat dissipation 2800 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 166 A. Maximum output current 263 A. No-overload use . Power 160 kW. Light-overload . Current 155 A. Power 132 kW. Heavy-duty use . Current 131 A. Power 110 kW. Noise level 71 dBA. Heat dissipation 3550 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 166 A. Maximum output current 294 A. No-overload use . Power 160 kW. Light-overload . Current 165 A. Power 160 kW. Heavy-duty use . Current 147 A. Power 132 kW. Noise level 71 dBA. Heat dissipation 4250 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 175 A. Maximum output current 326 A. No-overload use . Power 160 kW. Light-overload . Current 175 A. Power 160 kW. Heavy-duty use . Current 163 A. Power 160 kW. Noise level 71 dBA. Heat dissipation 4800 W. Air flow 540 m3/h. Frame size R7. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 315 A. Maximum output current 433 A. No-overload use . Power 315 kW. Light-overload . Current 290 A. Power 250 kW. Heavy-duty use . Current 216 A. Power 200 kW. Noise level 72 dBA. Heat dissipation 6150 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 353 A. Maximum output current 548 A. No-overload use . Power 355 kW. Light-overload . Current 344 A. Power 315 kW. Heavy-duty use . Current 274 A. Power 250 kW. Noise level 72 dBA. Heat dissipation 6650 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 396 A. Maximum output current 656 A. No-overload use . Power 400 kW. Light-overload . Current 387 A. Power 355 kW. Heavy-duty use . Current 328 A. Power 315 kW. Noise level 72 dBA. Heat dissipation 7400 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 445 A. Maximum output current 775 A. No-overload use . Power 450 kW. Light-overload . Current 426 A. Power 400 kW. Heavy-duty use . Current 387 A. Power 355 kW. Noise level 72 dBA. Heat dissipation 8450 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 488 A. Maximum output current 853 A. No-overload use . Power 500 kW. Light-overload . Current 482 A. Power 450 kW. Heavy-duty use . Current 426 A. Power 400 kW. Noise level 72 dBA. Heat dissipation 8300 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
ABB Single drive. ACS800 -02. Type Free-standing drives. Voltage 3AC525V-3AC690V . Rated current 560 A. Maximum output current 964 A. No-overload use . Power 560 kW. Light-overload . Current 537 A. Power 500 kW. Heavy-duty use . Current 482 A. Power 450 kW. Noise level 72 dBA. Heat dissipation 9750 W. Air flow 1220 m3/h. Frame size R8. Degree of protection IP21.
Ingetool Systems, SL don't assume any responsibility for the possible inaccuracy of any data contained within this site, but it is our constant endeavor to keep free of errors.
INGETOOL-SISTEMAS develops this platform to include the products and tools you wish.
Please, contact us.
INGETOOL-SISTEMAS, S.L.
Parque Empresarial Torneo
C/ Arquitectura 1, Torre 6, Pt. 8, Mod. 4
41015 Sevilla - Spain
Phone +34 95 431 13 91
Contact: info@multiselector.com
Copyright 2011-2015
New Drive-SelectionTool
X
From now, all the information most complete and updated in..
All the converters and its components, accessories, protections, contactors, cables, cabinets, etc...
X
Free 15 days trial
ConversionTool
circulo